The short answer

Five red flashes on a Trane furnace in Northern Virginia means the control board sensed a flame when there shouldn’t be one. Either gas is really burning when the furnace isn’t calling for heat, or the board is misreading its flame sensor: a sensor wire shorted to the metal, a grounded sensor, or a failing board. You can’t tell which from the hallway, so treat it as real. Don’t reset it, turn the thermostat off, and call.

What 5 flashes means on each Trane board

Swipe to see all columns →

Swipe to see all columns →

Furnace What you see What Trane says it means
Single-stage 80% furnaces (installer guide) Red light, 5 flashes Flame sensed when no flame should be present
Two-stage furnaces with a red and a green light (installer guide) Red light, 5 flashes Flame sensed when no flame should be present
Modulating furnaces (modulating furnace guide) Red light, 5 flashes; alert 34 Flame detected, should not be present
Furnaces with a number display (S9X installer guide) E05 Flame detected, should not be present
Link furnaces (Link furnace guide) E5.0 (ERR 034.00) Flame detected, should not be present. Trane files it as an internal lockout

Every other code on each board is in our Trane furnace error codes guide. A two-stage board flashes its last 4 faults again, newest first, when the power comes back on, and a number display keeps the last 6 under L6F. So a tech can still see a 5 that’s come and gone.

Two SwiftPro technicians in a Northern Virginia utility room, at the open furnace with the tank water heater behind them
Two of our techs at an open furnace, with the tank water heater behind them.

The $67 Heating Check

We check your furnace, heat pump or boiler before winter. Through December 31. See the offer

What to do right now

If you smell gas, don’t touch the furnace or any switch. Leave the house and call the gas company’s emergency line from outside.

If there’s no gas smell:

  • Count the flashes twice and write the number down, along with which light is flashing.
  • Turn the thermostat off. If you can still see the burners lit through the window with the thermostat off, shut the gas off at the furnace’s manual shutoff valve on the gas pipe, then turn off the furnace’s power. That order, gas first and power second, is from Trane’s owner instructions, and its single-stage guide says the same for a gas supply that won’t shut off.
  • Leave the front panel on. Trane’s page on a blinking furnace light says not to take it off while the furnace runs, and many furnaces have a door switch that cuts power and gas when it comes off.
  • Don’t reset it to get heat back. A flame the board can’t account for isn’t something a reset fixes, and it’s not a part to guess at.

What the tech checks

Trane’s chart for E05 in the S9X guide splits it on one question: is there a flame with no call for heat?

  • Yes, a real flame. Power and gas go off, the gas valve comes out, and the tech checks the valve’s inlet screen for moisture or debris. If there’s any, the next steps are checking for gas leaks and having the gas supplier check the gas. Then the drip leg, which Trane’s single-stage guide calls a sediment trap, in the gas line ahead of the gas valve. No drip leg, and one gets installed to the National Fuel Gas Code. A drip leg in place, and the gas valve gets replaced.
  • No flame. Then the board is reading flame current that isn’t there. If the board’s test pads show current, the flame sense wire is shorted to ground or the sensor is grounded. If they don’t, the board itself gets replaced.

What it usually comes down to

Swipe to see all columns →

Swipe to see all columns →

Cause What the tech finds Typical repair
The gas valve Gas getting through a valve that should be closed The tech prices it after testing
No drip leg Nothing in the gas line ahead of the valve to trap what comes down the pipe The tech prices it after testing
The flame sense wire A wire shorted to the furnace’s metal The tech prices it after testing
The flame sensor A grounded sensor $240 to $410 replaced
The control board A board reading a flame that isn’t there $550 to $1,180

Don’t confuse it with these

Furnace control board and wiring viewed in the open cabinet
A furnace control board and wiring.

More Trane codes and fixes

The system we put in first

Built to take a beating. Put in by our crew.

Heat lamps, snow and rain on one outdoor unit: that’s Trane’s own film. We’re a Trane Comfort Specialist, on Trane’s own dealer locator, and when you pick a Trane, our crew puts it in.

Films: Trane’s own.

Trane's film: a Trane outdoor unit on a dark lab stage under the Trane logo and "It's Hard To Stop A Trane."
Trane's film: a Trane outdoor unit under a spotlight against a bare wall.

What a visit costs

A diagnostic visit is $99, and you get the problem and the price in writing before any work starts. Our heating check is $67 per system, through December 31: furnace, heat pump or boiler. If you want every brand’s codes and lights in one place, our error codes and warning lights guide has them.

Book it

Book the heating check, call (703) 997-9757, or book online from goswiftpro.com/cookiesoffer and a box of warm cookies comes with the visit. Rated 5.0 stars across 1,138 reviews on Google, Angi, Yelp, the BBB and Facebook, Virginia Class A license 2705192276.

Questions people ask

What does 5 flashes mean on a Trane furnace?

The control board sensed a flame when no flame should be there. It’s either gas really burning when it shouldn’t, or the board misreading its flame sensor. Either way it’s a call for a tech.

What is error E05 on a Trane furnace?

The same fault on a furnace with a number display, like the S9X: flame detected that shouldn’t be present. On a Link furnace it’s E5.0, ERR 034.00 on the thermostat.

Is a Trane furnace flashing 5 times dangerous?

It can be, so treat it as real. If you smell gas, leave the house and call the gas company’s emergency line from outside. If not, turn the thermostat off and call. If the burners stay lit, Trane says shut the gas off at the furnace’s valve before the power.

Can I reset a Trane furnace with 5 flashes?

Don’t. A reset can clear the light, but it doesn’t explain a flame the board can’t account for. Leave it off and have it checked.

How much does it cost to fix 5 flashes on a Trane furnace?

The diagnostic is $99. A new flame sensor runs $240 to $410 and a control board $550 to $1,180. A gas valve, wiring or a drip leg is priced in writing after testing.