The short answer

Nine red flashes on a Trane furnace in Northern Virginia means one of two different things, depending on the board. On an older single-stage furnace with one red light, it’s an igniter relay fault. On a two-stage furnace with a red and a green light, it’s the inducer limit, a switch that opens when the flue gas runs too hot. Same count, different part, so know which board you have before anyone orders anything. Either way, it’s a call for a tech.

Which board do you have?

Look through the window in the furnace’s lower door. One red light is the single-stage board. A red and a green light is a two-stage board. A number display is an S9X or newer, and it shows E09 instead of flashing.

Swipe to see all columns →

Swipe to see all columns →

Furnace What you see What Trane says it means
Single-stage 80% furnaces (installer guide) Red light, 9 flashes Igniter relay fault
Two-stage furnaces with a red and a green light (installer guide) Red light, 9 flashes Open inducer limit
Modulating furnaces (modulating furnace guide) Red light, 9 flashes; alert 26 Inducer limit open: flue gas temperature too high, which Trane says can come from low airflow or a fan failure
Furnaces with a number display (S9X installer guide) E09 Open inducer limit switch, or the condensate pressure switch
Link furnaces (Link furnace guide) E9.1 (ERR 026.02), E9.2 (ERR 026.06), E9.3 (ERR 026.07) Inducer limit; condensate pressure switch; condensate lockout

The $67 Heating Check

We check your furnace, heat pump or boiler before winter. Through December 31. See the offer

One red light: the igniter relay

Trane’s single-stage guide calls 9 flashes an igniter relay fault. Its newer boards put the same fault under E6.3, and the S9X chart for that code checks for power at the board’s igniter terminals, then the harness, then the igniter itself, and replaces the board when the readings point there. Expect a tech to work the older board the same way. If the igniter checks out, it’s the board.

Two SwiftPro technicians at an open furnace in the utility closet of a Northern Virginia home, the water heater behind them
Two of our techs at an open furnace in a utility closet, with the water heater behind them.

Red and green lights: the inducer limit

On a two-stage board, 9 flashes is the inducer limit. Trane’s modulating furnace guide describes the same switch as flue gas temperature too high. Its chart for the same fault in the S9X guide says it’s normally caused by how the venting system was installed or applied, so the tech checks the vent pipes and where they end outside, clears anything blocking them, and checks the limit itself. Trane’s chart also lists the wrong limit switch, an inducer that isn’t working right, or a heat exchanger problem as possible causes.

Don’t mix it up with the high limit. Trane’s modulating guide puts the high limit on the heat exchanger running too hot, and that’s 4 flashes. The inducer limit watches the flue gas.

E09 can be the drain too

On a furnace with a number display, E09 covers the condensate pressure switch as well. Trane’s S9X guide says a blocked main drain, with an overflow standpipe higher than the bottom of the condensate trap, can trip it, and so can a pressure switch hose that isn’t trimmed to fit. In extreme cases, it can turn into an E04 rollout trip. On a Link furnace the drain codes are split out: E9.2 is the condensate switch, and 5 openings in one call for heat is E9.3, a one hour lockout. Trane says that’s normally a stoppage of condensate outside the furnace. Our 3 flashes and condensate drain guides cover the drain itself.

What it usually comes down to

Swipe to see all columns →

Swipe to see all columns →

Cause What the tech finds Typical repair
The igniter relay (one red light) A relay on the control board that’s failed $550 to $1,180
The igniter An igniter that’s open $240 to $410
The venting (red and green) A blocked vent, or one installed wrong The tech prices it after testing
The inducer or the limit An inducer not working right, or the wrong limit switch The tech prices it after testing
A blocked condensate drain (E09) A drain that isn’t flowing freely $175 to $420

What you can do

  • Count the flashes twice and write the number down, along with which light is flashing.
  • If your furnace vents through white plastic pipes out the wall or roof, make sure snow, ice and leaves aren’t blocking them. Don’t reach inside.
  • Check the filter. When a furnace locks out, Trane’s lockout page says the filter is the only thing to try yourself.
  • Leave the front panel on. Trane’s page on a blinking furnace light says not to take it off while the furnace runs, and many furnaces have a door switch that cuts power and gas when it comes off.
  • Don’t keep resetting it. If it comes back, the cause is still there.

If you smell gas, don’t touch the furnace or any switch. Leave the house and call the gas company’s emergency line from outside.

Gas furnace cabinet opened with the blower out and wiring visible
A furnace with the blower pulled out.

More Trane codes and fixes

The system we put in first

Built to take a beating. Put in by our crew.

Heat lamps, snow and rain on one outdoor unit: that’s Trane’s own film. We’re a Trane Comfort Specialist, on Trane’s own dealer locator, and when you pick a Trane, our crew puts it in.

Films: Trane’s own.

Trane's film: a Trane outdoor unit on a dark lab stage under the Trane logo and "It's Hard To Stop A Trane."
Trane's film: a Trane outdoor unit under a spotlight against a bare wall.

What a visit costs

A diagnostic visit is $99, and you get the problem and the price in writing before any work starts. Our heating check is $67 per system, through December 31: furnace, heat pump or boiler. If you want every brand’s codes and lights in one place, our error codes and warning lights guide has them.

Book it

Book the heating check, call (703) 997-9757, or book online from goswiftpro.com/cookiesoffer and a box of warm cookies comes with the visit. Rated 5.0 stars across 1,138 reviews on Google, Angi, Yelp, the BBB and Facebook, Virginia Class A license 2705192276.

Questions people ask

What does 9 flashes mean on a Trane furnace?

On a single-stage board with one red light, an igniter relay fault. On a two-stage board with a red and a green light, an open inducer limit. Check which board you have.

What is E09 on a Trane furnace?

An open inducer limit switch or condensate pressure switch. Trane says a blocked drain can trip it, so the drain is one of the first things a tech checks.

Is the inducer limit the same as the high limit?

No. The high limit watches the heat exchanger and shows as 4 flashes. The inducer limit watches the flue gas and shows as 9 flashes on a two-stage board.

Can I reset a Trane furnace with 9 flashes?

Don’t keep resetting it. Check the vent pipes outside for snow or leaves, and the filter, then call.

How much does it cost to fix 9 flashes on a Trane furnace?

The diagnostic is $99. A control board runs $550 to $1,180, an igniter $240 to $410, and a condensate drain repair $175 to $420. Venting work is priced in writing after testing.