The short answer
On a Trane Link furnace in Northern Virginia, a fault shows up two ways: a short E code on the furnace’s own display, and a longer ERR number on the thermostat, like ERR 022.01. Both come from the same table in Trane’s Link furnace guide, and we’ve sorted it by the ERR number so you can find yours. Most are a call for a tech; a few start with a filter, a vent pipe or a drain you can check yourself.
Where the codes show up
Per Trane’s Link furnace guide, the board’s display only has room for two digits, so it shows the main code and a tech reads the full one over Bluetooth with Trane’s Technician app. The thermostat shows them too; Trane’s guide names the SC360 and the UX360. Err 126 is a different thing, lost communication: our Err 126 guide covers it.
Trane’s table prints a few as 01.05 or 04.00, its charts as 001.05 or 004.00. Same codes.
The $67 Heating Check
We check your furnace, heat pump or boiler before winter. Through December 31. See the offer
Every Link furnace code, by ERR number
Swipe to see all columns →
Swipe to see all columns →
| ERR on the thermostat | Furnace shows | What Trane says | Where to start |
|---|---|---|---|
| 001.02 | E3.4 | Second stage pressure switch open | Vents and drain, then call (guide) |
| 001.03 | E3.3 | Second stage pressure switch shorted | Call |
| 001.04 | E3.2 | First stage pressure switch open | Vents and drain, then call (guide) |
| 001.05 | E3.1 | First stage pressure switch shorted | Call |
| 004.00 | E8.0 | Low flame sense; still running | Usually the flame sensor (guide) |
| SOP 004.50 | E28 | Supply air thermistor out of range | Call |
| SOP 004.52 | E27 | Return air thermistor out of range | Call |
| 010.00 | E6.3 | Igniter open | Call (guide) |
| 010.01 | E6.3 | Igniter relay failed | Call (guide) |
| 018.00 | E1.0 | Internal failure of the control board | Call |
| 018.05 | E9.4 | A control board that doesn’t match the furnace | Call |
| 022.00 | E2.2 | Recycles exceeded; one hour lockout | The filter, then call (guide) |
| 022.01 | E2.1 | Retries exceeded; one hour lockout | The filter, then call (guide) |
| 022.02 | E2.3 | First stage gas valve not powered when it should be, 10 times | Call (guide) |
| 022.04 | E3.5 | Second stage pressure switch open with the second stage gas valve powered | Call |
| 026.00 | E4.1 | Reverse airflow limit open | The filter, then call (guide) |
| 026.01 | E4.0 | High limit open | The filter, then call (guide) |
| 026.02 | E9.1 | Inducer limit open | Vents outside, then call (guide) |
| 026.06 | E9.2 | Condensate pressure switch open | The drain (guide) |
| 026.07 | E9.3 | Condensate lockout; one hour | The drain (guide) |
| 033.00 | E6.1 | Voltage reversed polarity | Call (guide) |
| 034.00 | E5.0 | Flame detected, should not be present | Leave it off and call (guide) |
| 087.00 | E4.2 | Rollout limit open | Call (guide) |
| 088.00 | E6.2 | Bad grounding | Call (guide) |
| 091.00 | E17 | Blower motor not answering the control | Call |
| 091.01 | E10 | A motor control lost communication with the furnace control | Call |
| 091.07 | E24 | Lost communication between two of the furnace’s control boards | Call |
| 091.08 | E10 | Inducer control board or inducer motor failed | Call |
| 091.12 | E18 | The control lost communication with the blower | Call |
| 092.00 | E12 | Open fuse | Call |
| 093.00 | E11 | A gas valve not powered when it should be | Call (guide) |
| 093.01 | E7.1 or E11 | A gas valve powered without a call for heat | Call (guide) |
| 093.02 | E11 | The redundant relay output not powered when it should be | Call (guide) |
| 093.03 | E7.2 | The redundant relay output on when it should be off | Call (guide) |
| 093.04 | E11 | Gas valve relay stuck closed | Call (guide) |
| 094.00 | E24 | Communication lost inside the furnace | Call |
| 114.02 | E13 | Blower motor ID doesn’t match the furnace | Call |
| 114.08 | None | No model number programmed into the board | Call |
| 114.09 | None | Invalid model number | Call |
| 114.10 | E14 | Configuration file error | Call |
| 161.03 | E26 | Return static pressure sensor out of range | Call |
| 161.04 | E25 | Accelerometer out of range or not responding | Call |
| None | E23 | Menu settings not received | Call |
The one hour lockouts
Per Trane’s charts, three of these stop the furnace for an hour: ERR 022.01 after 6 failed tries to light in one call for heat, ERR 022.00 after the flame drops out 10 times, and ERR 026.07 after the condensate switch opens 5 times. Other boards count differently: see our Trane furnace error codes guide.
What Trane’s charts point to
- Pressure switch codes (ERR 001.02 to 001.05). Trane’s chart says that in most cases the pressure switch isn’t the problem. Our 3 flashes guide covers the vent, the inducer and the drain.
- Condensate codes (ERR 026.06 and 026.07). Trane says these are normally caused by a stoppage of condensate outside the furnace, so the drain line is the first place to look.
- Blower communication codes (E17 and E18). Most likely a loose low voltage control wiring connection, per Trane’s chart.
What you can do
- Write down the full number, decimals and all.
- Check the filter. It’s on Trane’s lockout list of causes, and it’s the one thing Trane says to try yourself.
- For a pressure switch or inducer limit code, check that snow, ice and leaves aren’t blocking the white plastic vent pipes outside.
- Leave the front panel on. Trane’s page on a blinking furnace light says not to take it off while the furnace runs, and many furnaces have a door switch that cuts power and gas when it comes off.
- Don’t keep resetting it. A code that comes back means the cause is still there.
If you smell gas, don’t touch the furnace or any switch. Leave the house and call the gas company’s emergency line from outside.

More Trane codes and fixes
- Trane furnace error codes: every light and code, board by board
- 2 flashes: the lockout after too many tries to light
- 3 flashes: the pressure switch, the vent or the drain
- 4 flashes: the limit or rollout switch
- 5 flashes: flame sensed when there should be none
- 6 flashes: polarity, ground or the igniter
- 7 flashes: the gas valve circuit
- 8 flashes: a weak flame signal
- 9 flashes: the igniter relay or the inducer limit
- Trane furnace blowing cold air: what to check first
- Trane heat pump not heating: the outdoor unit side of a cold house
- Emergency heat on a Trane heat pump: when to switch it on
- Trane thermostat not working: a screen or a call for heat that isn’t right
- Trane thermostat says Wait: why it pauses before it runs
- Trane repair in Northern Virginia: book a tech
What a visit costs
A diagnostic visit is $99, and you get the problem and the price in writing before any work starts. Our heating check is $67 per system, through December 31: furnace, heat pump or boiler. If you want every brand’s codes and lights in one place, our error codes and warning lights guide has them.
Book it
Book the heating check, call (703) 997-9757, or book online from goswiftpro.com/cookiesoffer and a box of warm cookies comes with the visit. Rated 5.0 stars across 1,138 reviews on Google, Angi, Yelp, the BBB and Facebook, Virginia Class A license 2705192276.
Questions people ask
Where do I find the error code on a Trane Link furnace?
On the furnace’s display, which shows a short E code, and on the thermostat, which shows the longer ERR number. A tech reads the full code over Bluetooth with Trane’s app.
What does ERR 022.01 mean on a Trane thermostat?
Retries exceeded: the furnace failed to light 6 times in one call for heat and locked out for an hour. Check the filter, then call if it comes back.
What does ERR 026.06 mean on a Trane thermostat?
The condensate pressure switch opened. Trane says it’s normally a stoppage of condensate outside the furnace, so the drain line comes first.
What is a Trane Link furnace?
A communicating Trane furnace that reports its faults to the thermostat. Trane’s Link guide covers the kit that turns its S9V2 furnace into one.
How much does it cost to fix a Trane Link furnace error?
The diagnostic is $99. A flame sensor cleaning runs $95 to $180, a condensate drain repair $175 to $420, and a control board $550 to $1,180.