The controller
Rinnai tankless error codes,
and what each means
A Rinnai with a problem shows a number on the controller. Write it down with the model from the rating plate, because a few numbers mean different things on different lines.
Rinnai codes on every series (SENSEI, RE, V and RUS)
Rinnai’s code book gives these the same meaning on every line, give or take the wording.
Rinnai tankless error codes shared across series| Code | What it means | What to do |
|---|
| 10 | The air supply or exhaust is blocked; on a condensing unit, the condensate trap may be full | Check the vent caps outside for a blockage, then call: the condensate line and air filter get checked too |
|---|
| 11 | No ignition: the heater didn’t light | Check the gas is on, and on propane that there’s gas in the tank |
|---|
| 12 | Flame failure: it lit, then lost the flame | The same gas checks as 11. If it keeps coming back, call |
|---|
| 16 | The outlet water went over 203°F (the V Series calls it a warning) | Leave it off and call |
|---|
| 19 | An electrical grounding fault | A wiring check |
|---|
| 61 | The combustion fan | A fan repair |
|---|
Source: Rinnai Troubleshooting TWH Diagnostic Codes, 100000652. Codes vary by model and control board: the chart printed on your unit, or its manual, is the final word.
Rinnai codes that depend on the model line
Check the rating plate for the line first: a SENSEI (RX, RXP) and the non-SENSEI units (RE, REP, V, RUS) don’t always mean the same thing by the same number.
Rinnai tankless error codes by model line| Code | What it means | What to do |
|---|
| LC (LC0 to LC9, 00) | Scale building up in the heat exchanger | A flush. Newer units lock out; a reset buys about 70 hours |
|---|
| SS | Service soon: a flush reminder set at install | Book the flush. On a SENSEI RX it’s set for 6, 12 or 24 months |
|---|
| 14 | Overheat. SENSEI RX: the heat exchanger; RE and V: the thermal fuse | Call. Rinnai’s checks include hot spots on the heat exchanger from scale |
|---|
| 25 | SENSEI RX: the condensate pump accessory’s safety switch | It only shows with a condensate pump installed: check the pump, then call |
|---|
| 32 | RE: the outgoing water temperature sensor | Scale on the sensor is one cause: a cleaning or a new sensor |
|---|
| 52 | SENSEI RX: the gas valve. RE and V: the modulating solenoid valve signal | A gas valve repair |
|---|
| 63 | SENSEI RX on a recirculation loop: recirculation flow too low | The loop needs more than 0.4 gallons a minute: a pump or loop check |
|---|
| 72 | SENSEI RX: the flame rod. RE and V: the flame sensing device | On an RE, Rinnai says check the flame rod for carbon |
|---|
| 79 | RE, V and other non-SENSEI units: water found in the cabinet | Shut off the water to the heater and call a licensed pro |
|---|
Source: Rinnai SENSEI RX and RE technical sheets, linked from Rinnai’s product pages. Codes vary by model and control board: the chart printed on your unit, or its manual, is the final word.